logo-icon

Effect of temperature on lead-acid batteries

In the server room ‘UPS power system configuration’ construction, the battery is an indispensable part, but we can not ignore the temperature for the battery capacity and life of the impact of the following three stages of battery storage, discharge, float charging to explain.

Will be self-discharging, to 50% of the remaining capacity of the battery as a base point, in Figure 1, 20 ℃ storage time of 16 months in storage,: 30 ℃ storage time of 10.5 months, 40 ℃ storage time of 5 months. Approximately for every 1°C increase in temperature, the storage time decreases by 0.5 this day

 

During the discharge process, the temperature affects the conversion of chemical energy inside the battery, Figure 2 takes 0.1C discharge current as an example, at 10℃, the discharge capacity is about 90%; at 20℃, the discharge capacity is about 98%; at 25℃, the discharge capacity is 100%; at 30℃, the discharge capacity is about 102%. About every 1℃ rise, the discharge capacity decreases by 0.4-0.7%, and it is not a linear change.

2024060409340180

The battery is in the float charging stage most of the time during use. Figure 2, with a float charging voltage of 2.3V/Cel (the battery is composed of monoblocs, each monobloc cell is rated at 2V, for example, a 12V battery is composed of 6 monobloc cells, and the float charging voltage is 13.8V). At 20°C, the lifespan is about 10 years; at 25°C, the lifespan is about 9 years; at 30°C, the lifespan is about 7 years. For approximately every 1°C rise, the life decreases by 0.2-0.4 years and does not change linearly.

2024060409341859

By analysing the three stages in storage, discharge and float charging, during the use of the battery, pay attention to the impact of temperature on the battery, and do a good job of temperature control to prevent premature battery obsolescence. In GB50174-2017 data centre design specification, the battery operating environment temperature is 20-30 ℃, in YD/T 799-2010 communication valve regulated sealed lead-acid battery standard, the battery capacity at 25 ℃ is 100%. Therefore, it is recommended that you set the ambient temperature to 25°C in the configuration of the UPS power system in the server room.

2024060409342198

Please contact us for a specific quotation Forklift Battery Production and Customization-Shenzhen Firosla

Let’s communicate how to buy forklift batteries and customized lead-acid batteries for free consultation!

Professional production line, SGS Alibaba certification

 

-Forklift Battery

-Golf Cart Battery

-Motorcycle Battery

-Lead Acid Battery

-Lithium Battery

-Customized batteries

Whatsapp:856 63544834